Fuel Storage Tank Guide

flameshieldSearching for fuel tank dimensions and tank specifications? Hurtado.cc provides under-ground and above-ground fuel storage tanks per the specifications listed below. Most importantly, all of these tank designs include a 30-year structural warranty supported by the Steel Tank Institute. Please browse the features and specifications by clicking to expand/collapse the tables below.

If you are ready to proceed to pricing, please submit your Request for a Price Proposal.

Under-ground Storage Tanks
Permatank is an F-922 (Fiberglass Secondary Containment), UL-58 and UL-1746 labeled tank, designed for underground storage of flammable and combustible liquids.  These tanks are manufactured of carbon steel with an FRP jacket providing an interstitial monitoring space.

ACT-100 tanks are F-894 (External Corrosion Protection of Composite Steel USTs), UL-58 and UL-1746 labeled and designed for underground storage of flammable and combustible liquids. ACT-100 tanks are manufactured of double-wall carbon steel with a 100 mil FRP laminate coating without the need for external cathodic protection.

ACT-100U tanks are F-961 (External Corrosion Protection of Composite Steel USTs), UL-58 and UL-1746 labeled and designed for underground storage of flammable and combustible liquids. ACT-100U tanks are manufactured of double-wall carbon steel with a 70mil urethane coating without the need for external cathodic protection.

Above-ground Storage Tanks

Flameshield® tanks feature double-wall steel construction.  These tanks are UL142 labeled and 2-hr fire-resistant.

Fireguard® tanks feature double-wall steel construction, with a lightweight concrete insulating material between the inner and outer tank.  Fireguard tanks meet the “protected” tank designation and are UL2085 labeled.  These tanks offer 2-hour fire protection and are impact-resistant and ballistic-resistant.

The tables shown below describe the typical features and specifications offered with fuel storage tank systems applied to power generation applications.  Other configurations include:

  • Rectangular tanks.
  • Generator Sub-base Tanks (UL142 or UL2085)
  • Water and chemical storage tanks.
  • Dispensing equipment for fleet vehicles or plant operations.
  • Customized electronic level sensors, pumps and accessories.
  • Split tanks for consolidated fuel inventory.

Flameshield Fuel Storage Tanks - Specifications

Flameshield Features:
200-4,000 gallon capacity
Flameshield Features:
5,000-25,000 gallon capacity
Double wall, cylindrical or rectangular constructionDouble wall, cylindrical or rectangular construction
2-Hr fire-tested2-Hr fire-tested
Meets UL142 and NFPA30 requirementsMeets UL142 and NFPA30 requirements
Emergency vent, size determined by tank capacityEmergency vent, size determined by tank capacity
Stack vent, size determined by tank capacityStack vent, size determined by tank capacity
4" Fuel fill port with 7 gallon overspill containment and lockable capClay & Bailey overfill prevention valve
Krueger At-a-Glance fuel gaugeMorrison Clock Gauge/Hi Level Alarm
4" fitting with 1.5" fuel pickup fitting with drop tube and foot valve, set 6" from bottom of tankLadder and platform for easy tank access
4" fitting with 2" fuel return tube and diffuser.Krueger Leak Gauge, interstitial leak monitor
2 x 4" Spare fittingsTank saddles with anchor points
Float vent valve (during filling operation, signals when tank is reaching filled condition)4" fitting with 1.5" fuel pickup drop tube and foot valve, set 6" from bottom of tank
Tank saddles with anchor points4" fitting with 2" fuel return tube and diffuser.
Exterior finish: SP-6 blast with 5-7 mils polyurethane coat (optional finishes available for superior corrosion protection)2 x 4" Spare fittings
Required decals and placards
Exterior finish: SP-6 blast with 5-7 mils polyurethane coat (optional finishes available for superior corrosion protection)
Krueger Leak Gauge, interstitial leak monitorRequired decals and placards
Ladder for easy tank accessOptional ground loading with ball valve, check valve and 3" coupling with locking dust cap
30-Year warranty by Steel Tank Institute.30-Year warranty by Steel Tank Institute

Flameshield ModelCapacity
(gallons)
Vent Size
(stack/emergency)
DiameterLengthWeight
(approx, lbs.)
FS5005002" / 4"46"6'-2"1,400
FS100010002" / 4"64"6'-2"2,250
FS150015002" / 4"64"9'-1"3,050
FS200020002" / 4"64"12'-1"3,800
FS300030002" / 6"65"18'0"6,250
FS400040002" / 6"65"24'4"7,400
FS500050002" / 6"96"13'-6"8,750
FS600060002" / 8"96"16'-2"10,000
FS800080002" / 8"96"21'-6"11,850
FS10000100004" / 8"120"17'-3"14,750
FS12000120004" / 8"120"20'-8"16,100
FS15000150004" / 8"120"25'-9"19,200
FS20000200004" / 8"120"34'-4"24,250
FS25000250004" / 10"126"38'-10"29,850
FS30000300004" / 10"126"46'-6"34,350
FS40000400004" / 10"144"47'-6"50,800

Fireguard Fuel Storage Tanks - Specifications

Fireguard Features:
200-4,000 gallon capacity
Fireguard Features:
5,000-40,000 gallon capacity
"Protected" double wall, cylindrical or rectangular construction"Protected" double wall, cylindrical or rectangular construction
2-hour fire-tested, ballistic and vehicle-impact tested2-hour fire-tested, ballistic and vehicle-impact tested
Meets UL2085, UL142 and NFPA30 requirementsMeets UL2085, UL142 and NFPA30 requirements
Emergency vent, size determined by tank capacityEmergency vent, size determined by tank capacity
Stack vent, size determined by tank capacityStack vent, size determined by tank capacity
4" Fuel fill port with 7 gallon overspill containment and lockable capClay & Bailey overfill prevention valve
Krueger At-a-Glance fuel gaugeMorrison Clock Gauge/Hi Level Alarm
4" fitting with 1.5" fuel pickup fitting with drop tube and foot valve, set 6" from bottom of tankLadder and platform for easy tank access
4" fitting with 2" fuel return tube and diffuser.Krueger Leak Gauge, interstitial leak monitor
2 x 4" Spare fittingsTank saddles with anchor points
Float vent valve (during filling operation, signals when tank is reaching filled condition)4" fitting with 1.5" fuel pickup fitting with drop tube and foot valve, set 6" from bottom of tank
Tank saddles with anchor points4" fitting with 2" fuel return tube and diffuser.
Exterior finish: SP-6 blast with 5-7 mils polyurethane coat (optional finishes available for superior corrosion protection)2 x 4" Spare fittings
Required decals and placardsExterior finish: SP-6 blast with 5-7 mils polyurethane coat (optional finishes available for superior corrosion protection)
Krueger Leak Gauge, interstitial leak monitorRequired decals and placards
Ladder for easy tank accessOptional ground loading with ball valve, check valve and 3" coupling with locking dust cap
30-Year warranty by Steel Tank Institute30-Year warranty by Steel Tank Institute

Fireguard ModelCapacity
(gallons)
Vent Size
(stack/emergency)
Diameter
(primary tank)
LengthWeight
(approx, lbs.)
FG5005002" / 4"51"5'-4"3,500
FG100010002" / 4"64"6'-8"4,750
FG150015002" / 6"46-1/2"12'5,000
FG200020002" / 6"64"12'-8"7,750
FG300030002" / 6"64"18'9"10,500
FG400040002" / 8"64"24'9"13,250
FG500050002" / 8"96"14'-1"14,250
FG600060002" / 8"96"16'-9"18,250
FG800080002" / 8"96"22'-2"22,500
FG10000100004" / 8"120"17'-9"25,250
FG12000120004" / 8"120"21'-2"28,750
FG15000150004" / 8"120"26'-4"33,750
FG20000200003" / 10"120"34'-11"42,500
FG25000250003" / 10"120"43'-6"51,250
FG30000300003" / 10"126"47'-3"58,500
FG40000400004" / 10"138"52'-8"91,000
FG50000500004" / 10"138"65'-8"110,750